Supply, installation, testing and commissioning of Dry Air Scrubber each comprising match of electrostatic precipitation technology, dry type air cleaner to remove oil, dumbs, smoke and fumes from exhaust air, as per the Specifications.
Electrostatic Precipitator Module of following specificationsElectrostatic Precipitator Cabinet (i.e. Body) shall be made of 14 gauge(1.6mm) MS CRCA (Mild Steel Cold Rolled Close Annealed) sheet, Air leak Proof, Weather Proof, outdoor unit confirms to Ingress Protection standard and Electro Powder coated with 7 tank treatment Process, washable type aluminum mesh pre filters with SS304 frame, Ionizing- Collecting cell(s) shall be of one-piece construction minimum 16" inches deep in direction of airflow. All support framing 0.039", end plates 0.062", ionizer 0.039" and Both repelling and collector plates shall be 0.031" inch thick aluminum and rigidly retained in place with tubular spacers and tie rods. Ionizing electrodes shall be heavy duty and non-breakable rigidly supported both vertically and laterally. High voltage support insulators shall be of made of Teflon, glazed to enhance dielectric strength and retard tracking. Insulators shall be mounted out of the air stream, to reduce contaminant buildup. All high voltage electrical connections within each tier of cells, shall be between cells and automatically made when cells are installed. Average efficiency of 90% for single pass test based on ASHRAE MERV at flow rates of 800 -1500CFM per module. Power supplies shall be 100% solid state CE Listed and Pulse width modulation (PWM) based design The system should be fitted with interlock switch for safety. The system should allow connection to a fan section in Bidirectional configuration method of ESP unit installation and should conform to necessary electrical & fire safety standards
All units should have Arc Suppression & Auto Restart, Performance Indicator Lights to indicate the status of the air cleaning system. Power Consumption should not be more that 50 watts per ESP cell.
Operating Voltage : 220V, 50 Hz Ionizing Voltage : 12.5 to 13 KVDC Collector Cell Voltage : 6 to 6.5 KVDC and the ESP unit shall have necessary BMS connectivity features.Additional Information: